      <abstract>
        <p>医院层流净化空调系统担负着手术室、ICU 等洁净区域的空气品质保证任务，长时间处在高风量、高换气次数的工作状况 之中，能耗在医院建筑总用能中所占比例很大。本文就该类系统风机和水泵普遍使用定频运行、部分负荷时段能量浪费严重的问题 进行分析，整理出层流净化空调系统运行特点和能耗组成，说明变频调节与净化负荷的匹配机理，给出变频改造的技术路线、设备 选型思路和实测测点布置方法。根据运行参数的采集和对比来分析风机、水泵变频运行前后能耗的变化，并且考察洁净度、温湿度 等关键指标在调速运行中保障的情况。分析结果表明，在保证洁净等级不变的情况下，变频改造可以在低负荷时段取得较好的节电 量效果，改善系统的运行平稳性。文章还对变频运行过程中容易产生的谐波干扰、低频喘振等进行分析，并给出相应的优化和管理 建议，给同类医院净化工程节能设计及运行调适提供一定的借鉴。</p>