      <title-group>
        <article-title>海外输电线路接地电阻降阻回填技术应用分析</article-title>
      </title-group>
      <contrib-group>
        <contrib contrib-type="author">
          <string-name>张 锋 刘 敏 湖北省电力规划设计研究院有限公司 湖北武汉 430000</string-name>
        </contrib>
      </contrib-group>
      <pub-date pub-type="epub">
        <year>2026</year>
        <month>7</month>
      </pub-date>
      <issue>7</issue>
      <abstract>
        <p>海外输电线路建设中国外输电线路接地电阻控制重点难点问题在于由于地质、气候、土壤电阻率分布不均匀等原因，在高土壤电
阻率地区接地电阻偏大，难以达到设计要求，给输电线路运维带来很大困难，利用降阻回填技术，优化接地装置周边土壤导电性能、降低
接地电阻，是解决高电阻率地区接地不达标的有效方式。本文以东南亚某 220 kV 输电线路工程为案例分析国外输电线路接地电阻控制的重
点和难点问题，重点研究膨润土基复合降阻材料选型与配比优化、分层回填施工工艺及现场测试等关键技术。结果表明：采用优化后的降
阻回填材料及施工工艺可将接地电阻由初始的 18.5Ω降至 8.2Ω,满足不大于 10Ω的设计要求；且该材料经运行 12 个月后性能稳定，无明显腐
蚀情况，该技术具有施工简单、成本低、效果持久等优势，可为海外同类型高压输电线路接地治理工程提供工程参考与技术支撑。
关键词：接地电阻；降阻回填；输电线路</p>