        <article-title>银川市太阳能直驱直储耦合地源热泵供热系统设计及性能研究</article-title>
      </title-group>
      <contrib-group>
        <contrib contrib-type="author">
          <string-name>董娟 （银川科技学院 宁夏银川 750000）</string-name>
        </contrib>
      </contrib-group>
      <pub-date pub-type="epub">
        <year>2026</year>
        <month>6</month>
      </pub-date>
      <issue>6</issue>
      <abstract>
        <p>针对银川地区传统供热能耗高、碳排放大及常规地源热泵土壤热失衡问题，提出太阳能直驱直储耦合地源热泵供热系统。以银川市 900 ㎡住宅为对象，结合当地气象、地质条件完成负荷计算、设备选型与仿真分析。结果表明：建筑设计热负荷 54kW，考虑系统管网热损失后总热负荷 56.7kW；配置 360kW 光伏、120 ㎡集热器、45kW 热泵、80m³ 蓄热罐及732kWh 锂电，可实现多模式智能切换。系统平均制热 COP 为 3.51，供暖期土壤温降仅 0.95℃，静态投资回收期 6.8 年，综合节能率 72.3%。该系统能效高、土壤热稳定性好、经济环保效益突出，可为西北寒冷地区清洁供暖提供参考。</p>
      </abstract>